Close×

Vaisala product manager, Lars Stormbom MSc, explains how advanced control regimes such as Demand Controlled Ventilation (DCV) and free cooling are gaining in popularity as the pressure to reduce HVAC energy consumption continues to rise.

No amount of intelligence in the building automation system can provide assistance if the sensor measuring the actual conditions has drifted.

It is also not enough that accuracy requirements are met out of the box, the requirements should be maintained during the lifetime of the building.

Indoor air conditions are considered benign for sensors. On the other hand, sensors used in building automation are rarely calibrated or serviced once the system has been commissioned.

Mis-wired or faulty sensors are common, so at least one comparison measurement should be done during the system commissioning.

It is advisable to check the installed sensors after a couple of years against a reliable handheld instrument. Some measurements demand extra care. I will now discuss outdoor humidity and CO2 sensors in more detail.

Outdoor humidity measurement

Economisers can save energy in some climates by using free cooling from outdoor air. In humid climates the most important factor is the amount of humidity in the outdoor air, not the temperature. At 30°C the enthalpy changes from 30 kJ/kg to 96 kJ/kg when the relative humidity changes from dry to 95%RH.

According to ASHRAE standard 90.1, differential enthalpy control or fixed enthalpy control is recommended in economisers for hot and humid climates. The RH accuracy for control sensors should be <±5%RH.

While most sensors are specified to ±5%RH or better, this specification is out of the box. The ±5%RH should be maintained over lifetime of the system. Outdoor humidity measurements are more demanding. The sensors are subjected to high humidity, high winds, solar heating and pollution.

It makes sense to use one properly maintained, high-quality outdoor humidity sensor instead of multiple low quality sensors.

Maintenance includes, in addition to periodic checking of the measurement, regular cleaning of the radiation shield. Failure to do so may lead to temperature readings several °C higher and relative humidity values more than 10%RH lower than actual values.

The most important consideration is to use a sensor designed for outdoor use. Some sensors that look good on the data sheet can drift so much in outdoor conditions as to be unusable after a few months.

Vaisala achieved top results with three Vaisala HUMICAP sensors used outdoors for more than 12 years at the Vaisala outdoor test site in Vantaa, Finland. We still recommend periodic checking against a reliable handheld instrument at least every second year as conditions outdoors vary dramatically.

CO2 sensors

CO2 sensors are central in reducing energy consumption using DCV. As the measurement directly controls the amount of fresh air used accuracy requirements are tightening.

The Californian regulation CEC-400-2008-001-CMF requires a ±75ppm accuracy at 600ppm and 1000ppm including five years stability. ASHRAE standard 90.1 for green buildings requires a ±50ppm accuracy at 1000ppm.

This kind of accuracy will not be achieved with simple instruments relying on 400ppm background concentration compensation algorithms. The 1000ppm control CO2 concentration is too far from the supposed 400pm background CO2 concentration as sensitivity drift is also likely to build up over time.

Especially the ±50ppm requirement can be achieved only with dual beam or single beam-dual wavelength instruments (like the Vaisala CARBOCAP) that are regularly calibrated using calibration gases.

A calibration interval of two years is probably enough depending on the instrument type. For slightly lower requirements a five-year service or replacement regime may be enough as our research found when we tested 23 Vaisala CARBOCAP GM10 measurement modules.

Where outdoor CO2 sensors are used in order to control a 600ppm difference between indoor and outdoor CO2 concentrations, this single sensor becomes one of the most important sensors in the whole building.

Drift in this sensor will affect all the independent zones in the building. In conclusion, many HVAC instruments are used in order to save energy. To achieve projected energy savings the measurements have to perform properly during their whole lifetime. If something is worth measuring, it is worth measuring right.